Yogicab 3.5 Core Aluminium Conductor, PVC Insulated UN/Armoured Cable (IS : 1554 /P-1) (600-1100V)
Conductor Insulation Inner Sheath Un-armoured cable Wire / strip armoured cable Round wire armoured cable C.R. Current rating
Size with

strended

conductor

(mm)²

Nominal thickness of PVC          insulation Main / Neutral

(mm)

Minimum thickness of PVC inner sheath

(mm)

Nominal thickness of PVC outer sheath

(mm)

Approx. overall diameter

(mm)

Nominal dimension of G.I. flat strip

(mm)

Minimum thickness of PVC outer sheath

(mm)

Approx. overall diameter

(mm)

Nominal dimension of G.I. wire

(mm)

Minimum thickness of PVC outer sheath

(mm)

Approx. overall diameter

(mm)

DC resistance at 20° C

(Ohm/km)

In ground

(A)

In air

(A)

25/16 1.2 1.0 0.30 2.00 22.5 4 x 0.80 1.40 21.9 1.60 1.40 23.5 1.200 76 70
35/16 1.2 1.0 0.30 2.00 25.0 4 x 0.80 1.40 24.2 1.60 1.40 26.0 0.868 92 86
50/25 1.4 1.2 0.30 2.20 29.0 4 x 0.80 1.40 27.4 1.60 1.56 30.0 0.641 100 105
70/35 1.4 1.2 0.40 2.20 33.0 4 x 0.80 1.56 31.5 2.00 1.56 32.5 0.443 135 130
95/50 1.6 1.4 0.40 2.20 36.5 4 x 0.80 1.56 34.8 2.00 1.56 36.5 0.320 165 155
120/70 1.6 1.4 0.50 2.40 39.0 4 x 0.80 1.72 38.5 2.00 1.72 40.5 0.253 185 180
150/70 1.8 1.4 0.50 2.40 42.5 4 x 0.80 1.72 42.7 2.00 1.88 44.0 0.206 210 205
185/95 2.0 1.6 0.50 2.60 47.5 4 x 0.80 1.88 47.2 2.50 2.04 50.0 0.164 235 240
240/120 2.2 1.6 0.60 3.00 54.0 4 x 0.80 2.04 52.7 2.50 2.20 55.0 0.125 275 280
300/150 2.4 1.8 0.60 3.20 58.0 4 x 0.80 2.20 57.9 2.50 2.36 61.0 0.100 305 315
400/185 2.6 2.0 0.70 3.40 65.0 4 x 0.80 2.52 66.1 3.15 2.68 68.0 0.078 335 375