Cable Structure

Conductor :  Solid copper conductor, class 1 DIN VDE 0281,IEC 60228

Insulation :  PVC insulation compound TI-1

Colour :  Green/Yellow, Blue, Black, Brown, Gray, Orange, Pink, Red, Violet, White, Green, Yellow or other colours

Flame propagation :  Flame retardant test as per IEC 60332-1

Cable features

  • Good application of insulation
  • High current carrying capacity
  • Excellent resistant to moisture, abrasion, grace, oil
  • Excellent mechanical & electrical properties
  • harmonized acc. to European standards
  • Steam and boiling water resistant
  • Tested by SGS, EIL, RITES, NPC, INTERTEK

Technical Data

Operating Temp -20°c to max.+80°C
Nominal voltage HO5V-U : 300/500 V
HO7V-U : 450/750 V
Test voltage HO5V-U : 2000 V
HO7V-U : 2500 V
Insulation resistance Min. 10 MΩ x km
Min. bending radius 4 x cable diameter

Application

H05V-U, H07V-U :
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations

Standard length cable packing :
Coils 100 and 200 m in carton boxes, reels

Technical Data Table

HO5V-U (300/500 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 70°C
Lower limit Upper limit
sqmm mm mm mm Ω / km MΩkm
0.5 0.6 1.9 2.3 36.0 0.014
0.75 0.6 2.1 2.5 24.5 0.013
1 0.6 2.2 2.7 18.1 0.011
  • All are class 1 solid conductor
  • Insulation grade is TI1
HO7V-U (450/750 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 70°C
Lower limit Upper limit
sqmm mm mm mm Ω / km MΩkm
1.5 0.7 2.6 3.2 12.1 0.011
2.5 0.8 3.2 3.9 7.41 0.010
4 0.8 3.6 4.4 4.61 0.0087
6 0.8 4.1 5.0 3.08 0.0074
10 1.0 5.3 6.4 1.83 0.0072
  • All are class 1 solid conductor
  • Insulation grade is TI1