Cable features

  • Special heat resistant insulation
  • High current carrying capacity
  • Less heat energy radiation
  • Excellent resistant to moisture, abrasion, grace, oil
  • Insulation is highly thermal stable
  • Long flex life
  • Excellent mechanical & electrical properties
  • harmonized acc. to European standards
  • Tested by SGS, EIL, RITES, NPC, INTERTEK

Cable Structure

Conductor :  Multiple-wire, round copper conductor class 2, DIN VDE 0281, IEC 60228

Insulation :  Heat – resistant polyvinyl chloride (PVC) insulation

Colour :  Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours

Flame propagation :  Flame retardant test as per IEC 60332-1

Technical Data

Operating Temp -30°C to +90°C
Nominal voltage HO5V2-R : 300/500 V
HO7V2-R : 450/750 V
Test voltage HO5V2-R : 2000 V
HO7V2-R : 2500 V
Insulation resistance 20 MΩ x km
Min. bending radius 4 x cable diameter

Application

HO5V2-R, HO7V2-R :
For internal wiring of appliances as well as installation in an electrical conduit pipe either on or underneath plaster

Standard length cable packing :
Coils 100 and 200 m in carton boxes, reels

Technical Data Table

HO5V2-R (300/500 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 90°C
Lower limit Upper limit
sqmm mm mm mm Ω / km MΩkm
0.5 0.6 2.0 2.4 36.0 0.014
0.75 0.6 2.2 2.6 24.5 0.012
1 0.6 2.3 2.8 18.1 0.011
  • * Class 2 flexible conductor
  • ** Class 5 flexible conductor
HO7V2-R (450/750 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 90°C
Lower limit Upper limit
sqmm mm mm mm Ω / km MΩkm
1.5 0.7 2.7 3.3 12.1 0.010
2.5 0.8 3.3 4.0 7.41 0.0099
4 0.8 3.8 4.6 4.61 0.0082
6 0.8 4.3 5.2 3.08 0.0070
10 1.0 5.6 6.7 1.83 0.0067
16 1.0 6.4 7.8 1.15 0.0056
25 1.2 8.1 9.7 0.727 0.0053
35 1.2 9.0 10.9 0.524 0.0046