Cable Structure

Conductor :  EC copper class 5 and class 6 generally conforms to IEC 60228, DIN VDE 0281

Insulation :  EPR

Sheath :  LSZH (Low Smoke Zero Halogen) Gray, Orange, Black, Red, Blue

*Any other Color on specific request can also be supplied

Cable features

  • Zero halogen low smoke insulation
  • Ultra high performance flexible for longer life and added safety
  • High flame retardant properties
  • Outstanding toughness & durability
  • High resistance to cuts, tears & abrasion
  • Resistance to oil, solvents and chemicals
  • Excellent ozone and weather resistant

Technical Data

Fixed installation -20°c to max.+90°C
Nominal voltage 1100 V
Test voltage 3000 V
Insulation resistance Min. 10 MΩ x km
Min. bending radius 6 x cable diameter
Flame propagation Flame retardant test as per IEC 60332-1

Application

EPR/LSZH 0.6/1Kv 90°C :
Suitable for D.C. power supplies on Telecom equipment and power applications where flexibility is required

Shipboard and offshore marine use where a low smoke halogen free tinned flexible cable is required for safety and to meet Certification Society approvals

Standard length cable packing :
Coils 100, 200,300 and 500 m. in wooden reels

Technical Data Table

EPR/LSZ-H single core double insulated cable
Nominal cross sectional area of conductor Nominal insln thickness Nominal sheath thickness Overall cable diameter Max conductor resistance at 20°C
Lower limit Upper limit
sqmm mm mm mm mm Ω/km
10 1.2 1.8 7.8 10 1.91
16 1.2 1.9 9 11.5 1.21
25 1.4 2 10 13 0.780
35 1.4 2.2 11.5 14.5 0.554
50 1.6 2.4 13 17 0.386
70 1.6 2.6 15 19 0.272
95 1.8 2.8 17.5 21.5 0.206
120 1.8 3 19.5 24 0.161
150 2 3.2 21.5 26 0.129
185 2.2 3.4 23 29 0.106
240 2.4 3.5 27 32 0.0801
300 2.6 3.6 30 35 0.0641
400 2.8 3.8 33 39 0.0486
  • All are flexible conductor
  • Insulation material is EPR
  • Sheath material is LSZH