HO5V-R (450/750 V)  HO7V-R (300/500 V)

Cable Structure

Conductor Multiple-wire, round copper conductor class 2, DIN VDE 0281, IEC 60228
Insulation PVC insulation compound TI-1
Colour Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours
Flame propagation Flame retardant test as per IEC 60332-1

Technical Data

Operating Temp -20°C to max.+80°C
Nominal voltage HO5V-R : 300/500 V
HO7V-R : 450/750 V
Test voltage HO5V-R : 2000 V
HO7V-R : 2500 V
Insulation resistance Min. 10 MΩ x km
Min. bending radius 4 x cable diameter

Cable features

  • High current carrying capacity
  • Excellent resistant to moisture, abrasion, grace, oil
  • Longer Flex Life
  • Excellent mechanical & electrical properties
  • harmonized acc. to European standards
  • Steam and boiling water resistant
  • Tested by SGS, EIL, RITES, NPC, INTE

Application

H05V-R, H07V-R
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations

Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels

Technical DataTable - HO5V-U (450/750 V)

Size in mm2 Nos/ dia. (Nom.) Insulation Thickness in mm ( nom.) Outer Dia in mm (Appx.) Max. C.R in ohm/km Copper
0.5 7/0.30 0.60 2.20 36.00
0.75 7/0.37 0.60 2.30 24.50
1 7/0.43 0.60 2.70 18.10
  • All are class 2 stranded conductor
  • Insulation grade is TI1

HO7V-R (300/500 V)

Size in mm2 Nos/ dia. (Nom.) Insulation Thickness in mm ( nom.) Outer Dia in mm (Appx.) Max. C.R in ohm/km Copper
1.5 7/0.52 0.70 3.00 12.1
2.5 7/0.67 0.80 3.60 7.41
4 7/0.85 0.80 4.30 4.61
6 7/1.05 0.80 4.80 3.08
10 7/1.35 1.00 6.10 1.83
16 7/1.71 1.00 7.40 1.15
25 7/2.14 1.20 8.90 0.727
35 7/2.52 1.20 10.10 0.524
50 19/1.83 1.40 11.90 0.387
70 19/2.14 1.40 14.00 0.268
95 19/2.52 1.60 13.30 0.193
120 37/2.03 1.60 17.80 0.153
150 37/2.27 1.80 20.00 0.124
185 37/2.52 2.00 23.80 0.0991
240 61/2.24 2.20 26.50 0.0754
300 61/2.50 2.40 29.60 0.0601
400 61/2.88 2.60 34.00 0.047
500 61/3.23 2.80 37.70 0.0366
630 91/2.97 2.80 42.60 0.0283
  • All are class 2 stranded conductor
  • Insulation grade is TI1

call