H05VV-F, H05V2V2-F (300/500 V)

Cable Structure

Conductor Fine Stranded Copper (Class 5 - Flexible Plain Copper) to VDE 0295 IEC 60228
Insulation HO5VVF : PVC
HO5V2V2F : Heat Resistant PVC
Colour White, Black, Blue or as per party order

Technical Data

Operating Temp H05VV-F -20°c to +80°C
H05V2V2-F -20°c to +90°C
Nominal voltage H05VV-F : 300/500 V
H05V2V2-F : 450/750 V
Test voltage H05VV-F : 2.5KV
H05V2V2-F : 2.5KV
Insulation resistance Min. 20 MΩ x km
Min. bending radius 7 x cable diameter

Cable features

  • Special heat resistant insulation
  • High current carrying capacity
  • Less heat energy radiation
  • Longer flex life
  • High compatibility of cores
  • Excellent resistant to moisture, abrasion, grace, oil
  • Excellent mechanical & electrical properties
  • Insulation is highly thermal stable
  • Harmonized acc. to European standards
  • Tested by SGS, EIL, RITES, NPC, INTERTEK

Application

H05VV-F, H05V2V2-F
H05VV-F AND H05V2V2-F cordage is a flexible PVC insulated, PVC jacketed harmonized cord recommended for use in electronic and electrical equipment such as office.

Standard length cable packing:
100, 200, 500, 1000 m. in reels

H05VV-F, H05V2V2-F (300/500 V)

Nom. Sq.Area Copper Configuration Nominal insulation thickness Nominal Sheath Thickness in mm Appx.overall Diameter in mm Max Conductor Resistance at 20°C
2 core 3 core 4 core 5 core 2 core 3 core 4 core 5 core
sq mm Nos/ mm. (Nom.) mm mm mm mm mm mm mm mm mm Ω/km
0.75 24/0.200 0.60 0.80 0.80 0.80 0.90 6.20 6.50 7.10 8.00 26.00
1 32/0.200 0.60 0.80 0.80 0.90 0.90 7.20 7.60 8.50 9.30 19.50
1.5 30/0.250 0.70 0.80 0.90 1.00 1.10 7.80 8.45 9.50 10.55 13.30
2.5 50/0.250 0.80 1.00 1.00 1.10 1.20 9.40 9.95 11.10 12.35 7.98
4 56/0.300 0.80 1.10 1.20 1.20 1.40 10.60 11.40 12.50 14.10 4.95
  • All are class 5 flexible conductor
  • Insulation grade is TI2
  • Sheathing grade is TM2

  • All are class 5 flexible conductor
  • Insulation grade is TI3
  • Sheathing grade is TM3

Note:

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83

call