Yogicab PV Solar cables
Electrolytic tinned copper of class 5 as per (IEC 60228)
XLPO to operate at max. temp. of 120°C similar to (E16/E18)IEC 60502-1
XLPO / cross linked EVA solidly connected with insulation (visible layers)
Yogicab P V Solar cables size:xxxx spec.TUV 2Pfg 1169/08.2007 Mth/year.
Size in mm2 | Nom.Ins. Thickness in mm | Nom.Sheath. Thickness in mm | Appx. Overall Dia in mm | Tinned Copper D.C Conductor Resistance ohm./km | Current Carrying Capicity at 60 'C in Air (Amps.) | Permissible Short Circuit Current (Isc) 5 sec. (kA) |
---|---|---|---|---|---|---|
1.5 | 0.50 | 0.50 | 4.10 | 13.700 | 30 | 0.19 |
2.5 | 0.50 | 0.50 | 4.50 | 8.210 | 41 | 0.32 |
4 | 0.50 | 0.50 | 5.20 | 5.090 | 55 | 0.5 |
6 | 0.50 | 0.50 | 5.70 | 3.390 | 70 | 0.76 |
10 | 0.50 | 0.50 | 6.90 | 1.950 | 98 | 1.26 |
16 | 0.50 | 0.50 | 8.00 | 1.240 | 132 | 2 |
25 | 0.90 | 1.00 | 11.00 | 0.795 | 176 | 3.15 |
35 | 0.90 | 1.10 | 12.30 | 0.565 | 218 | 4.41 |
50 | 0.90 | 1.20 | 14.50 | 0.393 | 276 | 6.3 |
70 | 1.00 | 1.30 | 16.70 | 0.277 | 347 | 8.82 |
95 | 1.10 | 1.50 | 19.10 | 0.210 | 416 | 12 |
120 | 1.20 | 1.60 | 21.20 | 0.164 | 488 | 15.1 |
150 | 1.40 | 1.70 | 24.00 | 0.132 | 566 | 18.9 |
185 | 1.60 | 1.90 | 26.80 | 0.108 | 644 | 23.3 |
240 | 1.70 | 2.10 | 29.90 | 0.0817 | 775 | 30.4 |